Metrological Qualification of PD Analysers for Insulation Diagnosis of HVDC and HVAC Grids
Publicat a:Sensors. 23 (14): 6317- - 2023-07-01 23(14), DOI: 10.3390/s23146317
Autors: Garnacho, Fernando; Alvarez, Fernando; Elg, Alf-Peter; Mier, Christian; Lahti, Kari; Khamlichi, Abderrahim; Arcones, Eduardo; Kluess, Joni; Rodrigo Mor, Armando; Pakonen, Pertti; Vidal, Jose Ramon; Camunas, Alvaro; Rovira, Jorge; Vera, Carlos; Haider, Miran
Afiliacions
Resum
On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270.
Paraules clau
Indicis de qualitat
Impacte bibliomètric. Anàlisi de la contribució i canal de difusió
El treball ha estat publicat a la revista Sensors a causa de la seva progressió i el bon impacte que ha aconseguit en els últims anys, segons l'agència Scopus (SJR), s'ha convertit en una referència en el seu camp. A l'any de publicació del treball, 2023, es trobava a la posició , aconseguint així situar-se com a revista Q1 (Primer Cuartil), en la categoria Instrumentation.
Des d'una perspectiva relativa, i atenent a l'indicador de impacte normalitzat calculat a partir del Field Citation Ratio (FCR) de la font Dimensions, proporciona un valor de: 1.61, el que indica que, comparat amb treballs en la mateixa disciplina i en el mateix any de publicació, el situa com un treball citat per sobre de la mitjana. (font consultada: Dimensions Jul 2025)
Concretament, i atenent a les diferents agències d'indexació, aquest treball ha acumulat, fins a la data 2025-07-26, el següent nombre de cites:
- WoS: 2
- Scopus: 2
- Europe PMC: 2